H32S0T
Series | High Performance PLC |
IO Points | 16DI/16DO, Transistor NPN output |
Program Capacity | 48K |
Execution Speed | 0.05μs/basic instruction |
COM Port | Built-in 1*RS232+ 1*RS485 |
Protocol | Modbus RTU/ASCII, Haiwellbus high-speed protocol, Freedom protocol |
Built-in 2 communication ports (RS232 + RS485), can be extended to 5 communication ports. Supports 7 expansion modules at most.Support Haiwell cloud platform,can use Haiwell cloud to do remote programming for Haiwell PLC ,upload/download,firmware upgrade,self-diagnosis,monitor and debug. Easy for remote connection and monitoring the real-time data of the site. |
- Product Introduction
- Technical Specification
- File Download
Model | Power | DI | DO | Pulse Input | Pulse Output | Communication | Max Module | Dimension |
H32S0T | 24V DC | 16 | 16 Transistor NPN | 4 Channels A/B phase (8 points) 200Khz | 4 Channels A/B phase (8 points) 200Khz | RS232+RS485, up to 5ports | 7 | 131*95*82mm |
Terminal Wiring Diagram
Product DI specification
Item | Digital Input DI |
Input signal | Non-voltage contact or NPN/PNP contact |
Action driving | ON: 3.5 mA above OFF: below 1.5 mA |
Input impedance | About 4.3KΩ |
Input maximum current | 10mA |
Response time | Default 6.4ms,Configurable 0.8~51.2ms |
Isolation mode | Each Channel optical isolation |
Input indication | LED light means ON, dark means OFF |
Power supply | PLC internal power supply: DC power(sink or source)5.3mA@24VDC |
Digital input (DI) wiring diagram
Product DO specification
Item | Relay Output-R | NPN or PNP transistor output - T/P | |
maximum load | Resistance load | 2A/1 point,8A/4 point per COM | 0.5A/1 point,2A/4 point per COM |
Inductive load | 50VA | 5W/24VDC | |
Light load | 100W | 12W/24VDC | |
Min. load | 10mA | 2mA | |
Voltage specification | Below 250VAC,30VDC | 30VDC | |
Drive capability | Maximum 5A/250VAC | MAX 1A 10S | |
Response time | Off-on 10ms,On-off 5ms | Off→On 10μs, On→Off 120μs | |
Leakage current when route opened | --- | Below 0.1mA | |
Isolation mode | Mechanical isolation | Each Channel optical isolation | |
Output indication | LED light means ON , dark means OFF | ||
Power supply | PLC internal power supply 24VDC |
Digital output (DO) wiring diagram
Item | Specification | Declare | |
Execution speed | 0.05μs/basic instruction | ||
Program language | LD(ladder) + FBD(function block) + IL( instruction list) | Accord with IEC 61131-3 | |
Program capacity | 48K | ||
Storage Method | Flash ROM permanent storage, dispense with backup battery | ||
X | External input | X0~X1023 | Support edge catch and signal filtering set |
Y | External output | Y0~Y1023 | Power-off preserve output can be configured |
M | Auxiliary relay | M0~ M12287 | Power-off preserve area can be set freedom |
(default power-off preserve) M1536~M2047 | |||
T | Timer (output coil) | T0~T1023 | Power-off preserve area can be set freedom, time base: 10ms, 100ms, 1s be set freedom,T252~T255 1ms |
(default power-off preserve) T96~T127 | |||
C | Counter (output coil) | C0~C255 | Power-off preserve area can be set freedom |
(default power-off preserve) C64~C127 | |||
S | Step state bits | S0~S2047 | Power-off preserve area can be set Freedom |
(default power-off preserve) S156~S255 | |||
SM | System state bits | SM0~SM215 | |
LM | Local relay | LM~LM31 | |
AI | Analog input register | AI0~AI255 | Support quantities convert, sample times and zero point correct |
AQ | Analog output register | AQ0~AQ255 | Support quantities convert, power-off preserve output can be configured |
V | Internal data register | V0~V14847 | power-off preserve area can be set freedom |
(default power-off preserve) V1000~V2047 | |||
TV | Timer (Current value register) | TV0~TV1023 | Power-off preserve area can be set freedom, time base: 10ms, 100ms, 1s can be set freedom, T252~T255 1ms |
(default power-off preserve) TV96~TV127 | |||
CV | Counter (Current value register) | CV0~CV255 | Power-off preserve area can be set freedom, CV48~CV79 are 32 bits, Other are 16 bits |
(default power-off preserve) CV64~CV127 | |||
SV | System register | SV0~SV900 | |
Lv | Local Register | Lv0~Lv31 | |
P | Indexed addressing point | P0~P9, use for indirect addressing | |
I | Interrupt | I1-I52 | |
LBL | Lable | 255, use for program skip | |
Communication port | MPU built-in 2 communication port (RS232/RS485), Max 5 communication port (RS232/RS485) Extension | Can be program or networking (master/slave) | |
Communication protocol | Modbus RTU/ASCII protocol, freedom communication protocol, Haiwellbus speed communication protocol, Baud rate 1200~115200bps | ||
PLC network capacity | PLC communication address can be set external set, Max 254, support 1: N, N: 1, N: N network | ||
Real time clock (RTC) | Display: year /month /day /hour /minute /second /week | Built-in battery | |
Float point arithmetic instruction | Support within 32 bits float point arithmetic, integer/float point convert arithmetic | ||
Password protect | Support 3 level password protection: Program file password Program block password PLC hardware password and upload prohibited function |