T32S0R-e
Series | Standard PLC |
IO Points | T32S0R-e |
Program Capacity | 48K |
Execution Speed | 0.05μs/basic instruction |
COM Port | Built-in 1* Ethernet port+1*RS232 port+1*RS485 port, expandable up to 5 serial communication ports |
Protocol | Modbus TCP, Haiwellbus TCP, Modbus RTU/ASCII, Haiwellbus high speed protocol, freedom protocol |
The PLC with Ethernet port also has all the functions of the PLC of same type without Ethernet port, it also supports networking,programming and monitoring via ethernet. Support Haiwell cloud platform,can use Haiwell cloud to do remote programming for Haiwell PLC ,upload/download,firmware upgrade,self-diagnosis,monitor and debug. Easy for remote connection and monitoring the real-time data of the site. |
- Product Introduction
- Technical Specification
- File Download
Model | Power | DI | DO | Pulse Input | Pulse Output | Communication | Max Module | Dimension |
T32S0R-e | 24V DC | 16 | 16 Relay | 2 Channels A/B phase (4 points) 200KHz | / | RS232+RS485, up to 5ports | 7 | 131*95*82mm |
Terminal Wiring Diagram
Product DI specification
Item | Digital Input DI |
Input signal | Non-voltage contact or NPN/PNP contact |
Action driving | ON: 3.5 mA above OFF: below 1.5 mA |
Input impedance | About 4.3KΩ |
Input maximum current | 10mA |
Response time | Default 6.4ms,Configurable 0.8~51.2ms |
Isolation mode | Each Channel optical isolation |
Input indication | LED light means ON, dark means OFF |
Power supply | PLC internal power supply: DC power(sink or source)5.3mA@24VDC |
Digital input (DI) wiring diagram
Product DO specification
Item | Relay Output-R | NPN or PNP transistor output - T/P | |
maximum load | Resistance load | 2A/1 point,8A/4 point per COM | 0.5A/1 point,2A/4 point per COM |
Inductive load | 50VA | 5W/24VDC | |
Light load | 100W | 12W/24VDC | |
Min. load | 10mA | 2mA | |
Voltage specification | Below 250VAC,30VDC | 30VDC | |
Drive capability | Maximum 5A/250VAC | MAX 1A 10S | |
Response time | Off-on 10ms,On-off 5ms | Off→On 10μs, On→Off 120μs | |
Leakage current when route opened | --- | Below 0.1mA | |
Isolation mode | Mechanical isolation | Each Channel optical isolation | |
Output indication | LED light means ON , dark means OFF | ||
Power supply | PLC internal power supply 24VDC |
Digital output (DO) wiring diagram
Item | Specification | Declare | |
Execution speed | 0.05μs/basic instruction | ||
Program language | LD(ladder) + FBD(function block) + IL( instruction list) | Accord with IEC 61131-3 | |
Program capacity | 48K | ||
Storage Method | Flash ROM permanent storage, dispense with backup battery | ||
X | External input | X0~X1023 | Support edge catch and signal filtering set |
Y | External output | Y0~Y1023 | Power-off preserve output can be configured |
M | Auxiliary relay | M0~ M12287 | Power-off preserve area can be set freedom |
(default power-off preserve) M1536~M2047 | |||
T | Timer (output coil) | T0~T1023 | Power-off preserve area can be set freedom, time base: 10ms, 100ms, 1s be set freedom,T252~T255 1ms |
(default power-off preserve) T96~T127 | |||
C | Counter (output coil) | C0~C255 | Power-off preserve area can be set freedom |
(default power-off preserve) C64~C127 | |||
S | Step state bits | S0~S2047 | Power-off preserve area can be set Freedom |
(default power-off preserve) S156~S255 | |||
SM | System state bits | SM0~SM215 | |
LM | Local relay | LM~LM31 | |
AI | Analog input register | AI0~AI255 | Support quantities convert, sample times and zero point correct |
AQ | Analog output register | AQ0~AQ255 | Support quantities convert, power-off preserve output can be configured |
V | Internal data register | V0~V14847 | power-off preserve area can be set freedom |
(default power-off preserve) V1000~V2047 | |||
TV | Timer (Current value register) | TV0~TV1023 | Power-off preserve area can be set freedom, time base: 10ms, 100ms, 1s can be set freedom, T252~T255 1ms |
(default power-off preserve) TV96~TV127 | |||
CV | Counter (Current value register) | CV0~CV255 | Power-off preserve area can be set freedom, CV48~CV79 are 32 bits, Other are 16 bits |
(default power-off preserve) CV64~CV127 | |||
SV | System register | SV0~SV900 | |
Lv | Local Register | Lv0~Lv31 | |
P | Indexed addressing point | P0~P9, use for indirect addressing | |
I | Interrupt | I1-I52 | |
LBL | Lable | 255, use for program skip | |
Communication port | MPU built-in 2 communication port (RS232/RS485), Max 5 communication port (RS232/RS485) Extension | Can be program or networking (master/slave) | |
Communication protocol | Modbus RTU/ASCII protocol, freedom communication protocol, Haiwellbus speed communication protocol, Baud rate 1200~115200bps | ||
PLC network capacity | PLC communication address can be set external set, Max 254, support 1: N, N: 1, N: N network | ||
Real time clock (RTC) | Display: year /month /day /hour /minute /second /week | Built-in battery | |
Float point arithmetic instruction | Support within 32 bits float point arithmetic, integer/float point convert arithmetic | ||
Password protect | Support 3 level password protection: Program file password Program block password PLC hardware password and upload prohibited function |