T - Standard Series PLC

T60S0T-e

T60S0T-e

SeriesStandard PLC
IO Points36DI/24DO, Transistor NPN output
Program Capacity48K
Execution Speed0.05μs/basic instruction
COM PortBuilt-in 1* Ethernet port+1*RS232 port+1*RS485 port, expandable up to 5 serial communication ports
ProtocolModbus TCP, Haiwellbus TCP, Modbus RTU/ASCII, Haiwellbus high speed protocol, freedom protocol
The PLC with Ethernet port also has all the functions of the PLC of same type without Ethernet port, it also supports networking,programming and monitoring via ethernet. Support Haiwell cloud platform,can use Haiwell cloud to do remote programming for Haiwell PLC ,upload/download,firmware upgrade,self-diagnosis,monitor and debug. Easy for remote connection and monitoring the real-time data of the site.
  • Product Introduction
  • Technical Specification
  • File Download
ModelPowerDIDOPulse
Input
Pulse
Output
CommunicationMax
Module
Dimension
T60S0T-e24V DC3624 Transistor
NPN
2 Channels
A/B phase
(4 points)
200KHz
2 Channels
A/B phase
(4 points)
200KHz
Ethernet,
 RS232+RS485,
up to 5ports
7177*95*82mm



Terminal Wiring Diagram

T60S0T-e.jpg


Product DI specification

Item

Digital Input DI

Input signal

Non-voltage contact or NPN/PNP contact

Action driving

ON: 3.5 mA above OFF: below 1.5 mA

Input impedance

About 4.3KΩ

Input maximum current

10mA

Response time

Default 6.4ms,Configurable 0.8~51.2ms

Isolation mode

Each Channel optical isolation

Input indication

LED light means ON, dark means OFF

Power supply

PLC internal power supply: DC power(sink or source)5.3mA@24VDC

Digital input (DI) wiring diagram

Haiwell Industry Automation


Product DO specification

Item

 Relay Output-R

NPN or PNP transistor output - T/P

maximum load

Resistance load

2A/1 point,8A/4 point per COM

0.5A/1 point,2A/4 point per COM

Inductive load

50VA

5W/DC24V

Light load

100W

12W/DC24V

Min. load

10mA

2mA

Voltage specification

Below 250VAC,30VDC

30VDC

Drive capability

Maximum 5A/250VAC

MAX 1A 10S

Response time

Off-on 10ms,On-off 5ms

Off→On 10μs, On→Off 120μs

Leakage current when route opened

---

Below 0.1mA

Isolation mode

Mechanical isolation

Each Channel optical isolation

Output indication

LED light means ON , dark means OFF

Power supply

PLC internal power supply 24VDC

Digital output (DO) wiring diagram

Haiwell Industry Automation



ItemSpecificationDeclare
Execution speed0.05μs/basic instruction
Program language