H04DT

H04DT

SeriesTemperature Module
Input type4 Channels DS18B20 temperature
COM PortN/A
Remote I/O moduleN/A
4 Channel DS18B20 or SHT11 temperature and humidity sensor; It can be used as the extended module for any types of PLC Host; The conversion accuracy is 9 to 12 bits.
  • Product Introduction
  • Technical Specification
  • File Download
ModelPowerAIAOConversionCOMDimension
H04DT24V DC4 Channels DS18B20,RW1820 
temperature sensor, DS1990 sensor 
or SHT1x, SHT7x temperature & 
humidity sensor

9~12 bit/30*95*82mm




Terminal wiring diagram

Haiwell Industry Automation

Product specification

ITEMH04DT
Input interfaceSHT1x / SHT7x / DS18B20 / RW1820 sensor
Input Quantity4 Channels 4 points
Communication interfaceN/A
Communication speedN/A
Communication protocolN/A
Power supply modePLC host internal power supply
Messured distance≤200m wire resistance 50Ω
Messured rangeDS18B20 / RW1820 : -55 ~ +125
SHT1x / SHT7x : -40 ~ 123.8
   0~100%RH
Isolation typeNo isolation between channels
Analog & Digital optical isolation

Product wiring diagram

Haiwell Industry Automation


CR NumberH04DT Function Declare
00H (Read only)The low byte is the module code, and the high byte is the module version number.
01HCommunication address
02HCommunication protocols:The low 4-bit of the low bytes: 0 - N,8,2 For RTU,1 - E,8,1 For RTU
2 - O,8,1 For RTU3 - N,7,2 For ASCII4 - E,7,1 For ASCII5 - O,7,1 For ASCII6 - N,8, 1 For RTU    
The high 4-bit of the low bytes: 0 – 2400,1 – 4800,2 – 9600,3 – 19200,4 – 38400,5 – 57600,6 - 115200
03H~06HExtend module name
07H~08HDefault IP address: 192.168.1.111
09~0AH (Read only)Reserve
0BHHigh byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example, subnet mask 255.255.255.0,
 b3~b0=1110), low byte reserved
0CH~0EH (Read only)Reserve
0FH (Read only)Error code : 0-normal, 1-illegal firmware identity ,2-incomplete firmware, 3-system data access exception, 
4-no external 24V power supply
10H~13H (Read only)Temperature input value of channel 1~4 
14H~17H (Read only)Humidity input value of channel 1~4 
18H~1BHSignal type of channel 1~4 (0-DS18B20 / RW1820 / DS1990, 1-SHT1x / SHT7x)
1CHThe using identification of engineering value
1DH~20HThe data lower-limit of channel 1~4
21H~24HThe data upper-limit of channel 1~4
25H~28HA/D data bit of channel 1~4
29H~2CHzero point correction of channel 1~4 
2DH (Read only)Sensor disconnection alarm of channel 1~4, each bit indicates 1 channel, 0- normal, 1- disconnection
2EH~2FH (Read only)Reserve
 30H-3FHThe serial number of channel 1~4, each serial number uses 4 registers.
 40H-4FH (Read only)Reserve