H08DOR
Series | Digital Module |
DI/DO points | 8DO, Relay output |
COM Port | N/A |
Remote I/O module | N/A |
The 8 DO(relay outputs) can be used as the extension module for any types of PLC host; When a extension module hanging at the back of thehost through the parallel bus, it can be powered by the inner 24VDC on the host. |
- Product Introduction
- Technical Specification
- File Download
Model | Power | DI | DO | Communication | Dimension |
H08DOR | 24V DC | 8 Relay | N/A | 30*95*82mm |
Terminal wiring diagram
Product DO specification
Item | Relay Output-R | NPN or PNP transistor output - T/P | |
maximum load | Resistance load | 2A/1 point,8A/4 point per COM | 0.5A/1 point,2A/4 point per COM |
Inductive load | 50VA | 5W/24VDC | |
Light load | 100W | 12W/24VDC | |
Min. load | 10mA | 2mA | |
Voltage specification | Below 250VAC,30VDC | 30VDC | |
Drive capability | Maximum 5A/250VAC | MAX 1A 10S | |
Response time | Off-on 10ms,On-off 5ms | Off→On 10μs, On→Off 120μs | |
Leakage current when route opened | --- | Below 0.1mA | |
Isolation mode | Mechanical isolation | Each Channel optical isolation | |
Output indication | LED light means ON , dark means OFF | ||
Power supply | PLC internal power supply 24VDC |
Digital Output (DO) wiring diagram
No CR data