H08TC2

H08TC2

SeriesTemperature Module
Input type8 thermocouple
COM PortBuilt-in 1*RS485
Remote I/O moduleSupported
8 channels thermocouple input, A/D hardware conversion accuracy: 16 bits; Support various types of signals: S, K, T, E, J, B, N, R, Wre3/25, Wre5/26, [0,20]mV, [0,50]mV, [0,100]mV; It can be used as the extended module for any types of PLC host; With the RS485 communication port, it can also be used as remote IO; When a extended module hanging at the back of the host though the parallel bus, it can be powered by the inner 24VDC on the host; It must be powered by external 220VAC when capacity of the inner 24VDC power supply is insufficient; When the module was used as remote I/O through serial bus, it must be powered by external 220VAC supply.
  • Product Introduction
  • Technical Specification
  • File Download
ModelPowerAIAOConversionCOMDimension
H08TC2220V AC8 thermocouple
16 bitRS48570*95*82mm

Terminal wiring diagram 

Haiwell Industry Automation

Product specification

ItemThermocuople input
Input rangeS,K, T, E, J ,B, N, R, Wre3/25, Wre5/26, [0-20]mV, [0-50]mV, [0-100]mV
Resolution0.1
Input impedance6MΩ
Max range±5V
Input indicationLED light means normal, dark means break OFF
Response time560ms/4 Channel, 880ms/8 Channel
Digital input range16 bits, Code range: 0~32000
Precision0.1% F.S
Power supplyMPU use internal power supply, Extension module use external 
power supply 24VDC ±10% 5VA
Isolation modeOpto-electric isolation, Non-isolation between Channel ,between 
analog and digital is opto-electric isolation
Power consumption24VDC ±20%, 50mA(Max)

Product input wiring diagram

Haiwell Industry Automation


CR NumberFunction Declare
H08TC2
00H (Read only)The low byte is the module code, and the high byte is the module version number.
01HCommunication address
02HCommunication protocol: The low 4-bit of the low bytes:0 - N,8,2 For RTU1 - E,8,1 For RTU
2 - O,8,1 For RTU
3 - N,7,2 For ASCII4 - E,7,1 For ASCII5 - O,7,1 For ASCII6 - N,8, 
1 For RTU       
The high 4-bit of the low bytes: 0 – 24001 – 48002 – 96003 – 192004 – 38400
5 – 57600
6 - 115200
03H~06HExtend module name
07H~08HDefault IP address: 192.168.1.111
09~0AH (Read only)Reserve
0BHHigh byte subnet mask(b3~b0,1 indicates 255,0 indicates 0 , for example, subnet mask 
255.255.255.0, b3~b0=1110), low byte Reserved
0CH~0EH (Read only)Reserve
0FH (Read only)Error code: 0-Normal, 1-Illegally firmware identity, 2-Incomplete firmware, 3-System data access
 exception, 4-No external 24V power supply
10H (Read only)The input value of channel 1
11H (Read only)The input value of channel 2
12H (Read only)The input value of channel 3
13H (Read only)The input value of channel 4
14H (Read only)The input value of channel 5
15H (Read only)The input value of channel 6
16H (Read only)The input value of channel 7
17H (Read only)The input value of channel 8
18HThe signal type of channel 1, note 4
19HThe signal type of channel 2, note 4
1AHThe signal type of channel 3, note 4
1BHThe signal type of channel 4, note 4
1CHThe signal type of channel 5, note 4
1DHThe signal type of channel 6, note 4
1EHThe signal type of channel 7, note 4
1FHThe signal type of channel 8, note 4
20HUse the engineering value mark, note 6
21HThe lower limit in engineering value of channel 1
22HThe lower limit in engineering value of channel 2
23HThe lower limit in engineering value of channel 3
24HThe lower limit in engineering value of channel 4
25HThe lower limit in engineering value of channel 5
26HThe lower limit in engineering value of channel 6
27HThe lower limit in engineering value of channel 7
28HThe lower limit in engineering value of channel 8
29HThe upper limit in engineering value of channel 1
2AHThe upper limit in engineering value of channel 2
2BHThe upper limit in engineering value of channel 3
2CHThe upper limit in engineering value of channel 4
2DHThe upper limit in engineering value of channel 5
2EHThe upper limit in engineering value of channel 6
2FHThe upper limit in engineering value of channel 7
30HThe upper limit in engineering value of channel 8
31HThe sampling frequency of channel 1, note 1
32HThe sampling frequency of channel 2, note 1
33HThe sampling frequency of channel 3, note 1
34HThe sampling frequency of channel 4, note 1
35HThe sampling frequency of channel 5, note 1
36HThe sampling frequency of channel 6, note 1
37HThe sampling frequency of channel 7, note 1
38HThe sampling frequency of channel 8, note 1
39HThe zero point correction value of  channel 1
3AHThe zero point correction value of  channel 2
3BHThe zero point correction value of  channel 3
3CHThe zero point correction value of  channel 4
3DHThe zero point correction value of  channel 5
3EHThe zero point correction value of  channel 6
3FHThe zero point correction value of  channel 7
40H
41H (Read only)Channel 1~8 input disconnection alarm, note 5
42H~4FH (Read only)Reserve

Note: 

1. Sampling frequency:0 - 2 times、1 - 4 times、2 - 8 times、3 - 16 times、4 - 32 times、5 - 64 times、6 - 128 times、7 - 256 times

2. Signal type:0 - [4,20]mA、1 - [0,20]mA 、2 - [1,5]V、3 - [0,5]V、4 - [0,10]V、5 - [-10,10]V

3. The signal type of thermal resistance:0 - Pt100、1 - Pt1000、2 - Cu50、3 - Cu100

4. The signal type of thermocouple:0 - S、1 - K、2 - T、3 - E、4 - J、5 - B、6 - N、7 - R、8 – Wre3/25、9- Wre5/26、10 - [0,20]mV、11 - [0,50]mV、12 - [0,100]mV

5. Disconnection alarm:Each bit indicates 1 channel, 0-normal, 1-disconnection

6. Use the engineering value mark:Each bit indicates 1 channel, 0-No, 1-Yes

7. Channel indicator status:Each bit indicates 1 channel, 0-off, 1-on

8. Power-off output mark:Each bit indicates 1 channel, 0-No, 1-Yes

9. The output flag while power supply lost: each bits signify 1 Channel ,0-No,1-Yes