H24DI-e

H24DI-e

SeriesDigital Module
DI/DO points24DI
COM PortBuilt-in 1*Ethernet port+1*RS485 port
Remote I/O moduleSupported
The expansion module with Ethernet port also has all the functions of the expansion module of same type without Ethernet port, it also supports Haiwell cloud platform,can use Haiwell cloud to do remote programming for Haiwell PLC ,upload/download,firmware upgrade,self-diagnosis,monitor and debug. Easy for remote connection and monitoring the real-time data of the site.
  • Product Introduction
  • Technical Specification
  • File Download
ModelPowerDIDOCommunicationDimension
H24DI-e24V DC24
RS48593*95*82mm

Terminal wiring diagram

H24DI-e.jpg

Product DI specification

ItemDigital Input DI
Input signalNon-voltage contact or NPN/PNP contact
Action drivingON: 3.5 mA above OFF: below 1.5 mA
Input impedanceAbout 4.3KΩ
Input maximum current10mA
Response timeDefault 6.4ms,Configurable 0.8~51.2ms
Isolation modeEach Channel optical isolation
Input indicationLED light means ON, dark means OFF
Power supplyPLC internal power supply: DC power(sink or source)5.3mA@24VDC

Digital input (DI) wiring diagram

Haiwell Industry Automation



CR NumberFunction Declare
H24DI
00H (Read only)The low byte is the module code, and the high byte is the module version number.
01HCommunication address
02HCommunication protocols:The low 4-bit of the low bytes: 0 - N,8,2 For RTU1 - E,8,1 For RTU
2 - O,8,1 For RTU
3 - N,7,2 For ASCII4 - E,7,1 For ASCII5 - O,7,1 For ASCII6 - N,8, 1 For 
RTU       
The high 4-bit of the low bytes: 0 – 24001 – 48002 – 96003 – 192004 – 38400
5 – 57600
6 - 115200
03H~06HExtend module name
07H~08HDefault IP address: 192.168.1.111
09~0AH (Read only)Reserve
0BHHigh byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example, subnet mask 
255.255.255.0, b3~b0=1110), low byte reserved
0CH~0EH (Read only)Reserve
0FH (Read only)Error code : 0-normal, 1-illegal firmware identity ,2-incomplete firmware, 3-system data access
 exception, 4-No external 24V power supply
10H~4FH (Read only)DI channel 1~64 input value
50H~8FHDO channel 1~64 output value
90HFiltering time of DI ms, 0 - 0.81 - 1.62 - 3.23 - 6.44 - 12.85 - 25.66 - 51.2
91H~9FH (Read only)Reserve