H32DT

H32DT

SeriesTemperature Module
Input type32 Channels DS18B20 temperature
COM PortBuilt-in 1*RS485
Remote I/O moduleSupported
32 channels DS18B20, the conversion accuracy is 9 to 12 bits; It can be used as the extended module for any types of PLC host.
  • Product Introduction
  • Technical Specification
  • File Download
ModelPowerAIAOConversionCOMDimension
H32DT24V DC32 Channels DS18B20, RW1820
 temperature sensor, DS1990 sensor

9~12 bitRS48530*95*82mm

Terminal wiring diagram 

Haiwell Industry Automation

Product specification

ITEMH32DT
Input interfaceDS18B20, RW1820 sensor
Input Quantity2 channels, each channel 16points
Communication interfaceRS485
Communication speed2400~115200bps baud rate
Communication protocolstandard Modbus
Power supply modePLC host internal power supply
or independent external supply of 24VDC
Messured distance≤500m (wire resistance 50Ω)
Messured range -55 ~ +125
Isolation typeNo isolation between channels
Analog & Digital optical isolation

Product wiring diagram

Haiwell Industry Automation



CR NumberH32DT Function Declare
00H (Read only)The low byte is the module code, and the high byte is the module version number.
01HCommunication address
02HCommunication protocols:The low 4-bit of the low bytes: 0 - N,8,2 For RTU1 - E,8,1 For RTU
2 - O,8,1 For RTU
3 - N,7,2 For ASCII4 - E,7,1 For ASCII5 - O,7,1 For ASCII6 - N,8, 1 For RTU    
The high 4-bit of the low bytes: 0 – 24001 – 48002 – 96003 – 192004 – 38400,
 
5 – 576006 - 115200
03H~06HExtend module name
07H~08HDefault IP address: 192.168.1.111
09~0AH (Read only)Reserve
0BHHigh byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example, subnet mask
 255.255.255.0, b3~b0=1110), low byte reserved
0CH~0EH (Read only)Reserve
0FH (Read only)Error code : 0-normal, 1-illegal firmware identity ,2-incomplete firmware, 3-system data access 
exception, 4-no external 24V power supply
10H~1FH (Read only)Temperature value in 1~16 path of channel 1 
20H~2FH (Read only)Temperature value in 1~16 path of channel 2 
30HA/D data bits of channel 1
31HA/D data bits of channel 2
32H (Read only)Temperature disconnection alarm in 1~16 path of channel 1, each bit indicates 1 channel, 
0- normal, 1- disconnection.
33H (Read only)Temperature disconnection alarm in 1~16 path of channel 2, each bit indicates 1 channel,
 0- normal, 1- disconnection.
34HConfiguration number of channel 1
35HConfiguration number of channel 2.
36~75HThe serial numbers in 1~16 path of channel 1, each serial number uses 4 registers.
76~B5HThe serial numbers of 1~16 path of channel 2, each serial number uses 4 registers.
B6~C5H (Read only)Reserve
C6H (Read only)Channel 1 clears the power-off counts in the configuration
C7H (Read only)Channel 2 clears the power-off counts in the configuration