S08AI

S08AI

SeriesAnalog Module
AI/AO points8AI
COM PortBuilt-in 1*RS485
Remote I/O moduleSupported
8 channels analog input, A/D hardware conversion accuracy: 12 bits; Support 6 types of signals:[4,20]mA、[0,20]mA、[1,5]V、[0,5]V、[0,10]V、[-10,10]V; It can be used as the extended module for any types of PLC host; With the RS485 communication port, it can also be used as remote IO; When a extended module hanging at the back of the host though the parallel bus, it can be powered by the inner 24VDC on the host; It must be powered by external 24VDC when capacity of the inner 24VDC power supply is insufficient; When the module was used as remote I/O through serial bus, it must be powered by external 24VDC supply.
  • Product Introduction
  • Technical Specification
  • File Download
ModelPowerAIAOConversionCOMDimension
S08AI24V DC8
12 bitRS48593*95*82mm

Terminal wiring diagram

Haiwell Industry Automation

Product AI specification

ItemVoltage InputCurrent Input
Input range-10V ~
+10V
0V ~
+10V
0V ~
+5V
1V ~
+5V
0 ~
20mA
4 ~
20mA
Resolution5mV2.5mV1.25mV1.25mV5μA5μA
Input impedance6MΩ250Ω
Max input range±13V±30mA
Input indicationLED light means normal, dark means break OFF
Response time5ms/4 Channel
Digital input range12 bits, Code range: 0~32000(H series module 16 bits A/D convert)
Precision0.2% F.S
Power supplyMPU use internal power supply, Extension module use external 
power supply 24VDC ±10% 5VA
Isolation modeOpto-electric isolation, Non-isolation between Channel ,between analog and digital
 is opto-electric isolation
Power consumption24VDC ±20%,100mA(Max)

Analog input (AI) wiring diagram

Haiwell Industry Automation



CR NumberFunction Declare
S08AI
00H (Read only)The low byte is the module code, and the high byte is the module version number.
01HCommunication address
02HCommunication protocol: The low 4-bit of the low bytes:0 - N,8,2 For RTU1 - E,8,1 For RTU
2 - O,8,1 For RTU
3 - N,7,2 For ASCII4 - E,7,1 For ASCII5 - O,7,1 For ASCII6 - N,8, 
1 For RTU       
The high 4-bit of the low bytes: 0 – 24001 – 48002 – 96003 – 192004 – 38400
5 – 57600
6 - 115200
03H~06HExtend module name
07H~08HDefault IP address: 192.168.1.111
09~0AH (Read only)Reserve
0BHHigh byte subnet mask(b3~b0,1 indicates 255,0 indicates 0 , for example, subnet mask 
255.255.255.0, b3~b0=1110), low byte Reserved
0CH~0EH (Read only)Reserve
0FH (Read only)Error code: 0-Normal, 1-Illegally firmware identity, 2-Incomplete firmware, 3-System data access
 exception, 4-No external 24V power supply
10H (Read only)The input value of channel 1
11H (Read only)The input value of channel 2
12H (Read only)The input value of channel 3
13H (Read only)The input value of channel 4
14H (Read only)The input value of channel 5
15H (Read only)The input value of channel 6
16H (Read only)The input value of channel 7
17H (Read only)The input value of channel 8
18HThe signal type of channel 1, note 2
19HThe signal type of channel 2, note 2
1AHThe signal type of channel 1, note 2
1BHThe signal type of channel 4, note 2
1CHThe signal type of channel 5, note 2
1DHThe signal type of channel 6, note 2
1EHThe signal type of channel 7, note 2
1FHThe signal type of channel 8, note 2
20HUse the engineering value mark, note 6
21HThe lower limit in engineering value of channel 1
22HThe lower limit in engineering value of channel 2
23HThe lower limit in engineering value of channel 3
24HThe lower limit in engineering value of channel 4
25HThe lower limit in engineering value of channel 5
26HThe lower limit in engineering value of channel 6
27HThe lower limit in engineering value of channel 7
28HThe lower limit in engineering value of channel 8
29HThe upper limit in engineering value of  channel 1
2AHThe upper limit in engineering value of  channel 2
2BHThe upper limit in engineering value of  channel 3
2CHThe upper limit in engineering value of  channel 4
2DHThe upper limit in engineering value of  channel 5
2EHThe upper limit in engineering value of  channel 6
2FHThe upper limit in engineering value of  channel 7
30HThe upper limit in engineering value of  channel 8
31HThe sampling frequency of  channel 1, note 1
32HThe sampling frequency of  channel 2, note 1
33HThe sampling frequency of  channel 3, note 1
34HThe sampling frequency of  channel 4, note 1
35HThe sampling frequency of  channel 5, note 1
36HThe sampling frequency of  channel 6, note 1
37HThe sampling frequency of  channel 7, note 1
38HThe sampling frequency of  channel 8, note 1
39HThe zero point correction value of channel 1
3AHThe zero point correction value of channel 2
3BHThe zero point correction value of channel 3
3CHThe zero point correction value of channel 4
3DHThe zero point correction value of channel 5
3EHThe zero point correction value of channel 6
3FHThe zero point correction value of channel 7
40HThe zero point correction value of channel 8
41H (Read only)Channel 1~8 input disconnection alarm, note 5
42H~4FH (Read only)Reserve

Note: 

1. Sampling frequency:0 - 2 times、1 - 4 times、2 - 8 times、3 - 16 times、4 - 32 times、5 - 64 times、6 - 128 times、7 - 256 times

2. Signal type:0 - [4,20]mA、1 - [0,20]mA 、2 - [1,5]V、3 - [0,5]V、4 - [0,10]V、5 - [-10,10]V

3. The signal type of thermal resistance:0 - Pt100、1 - Pt1000、2 - Cu50、3 - Cu100

4. The signal type of thermocouple:0 - S、1 - K、2 - T、3 - E、4 - J、5 - B、6 - N、7 - R、8 – Wre3/25、9- Wre5/26、10 - [0,20]mV、11 - [0,50]mV、12 - [0,100]mV

5. Disconnection alarm:Each bit indicates 1 channel, 0-normal, 1-disconnection

6. Use the engineering value mark:Each bit indicates 1 channel, 0-No, 1-Yes

7. Channel indicator status:Each bit indicates 1 channel, 0-off, 1-on

8. Power-off output mark:Each bit indicates 1 channel, 0-No, 1-Yes

9. The output flag while power supply lost: each bits signify 1 Channel ,0-No,1-Yes