S08XA2-e

S08XA2-e

SeriesAnalog Module
AI/AO points4AI/4AO
COM PortBuilt-in 1*Ethernet port+1*RS485 port
Remote I/O moduleSupported
The expansion module with Ethernet port also has all the functions of the expansion module of same type without Ethernet port, it also supports Haiwell cloud platform,can use Haiwell cloud to do remote programming for Haiwell PLC ,upload/download,firmware upgrade,self-diagnosis,monitor and debug. Easy for remote connection and monitoring the real-time data of the site.
  • Product Introduction
  • Technical Specification
  • File Download
ModelPowerAIAOConversionCOMDimension
S08XA2-e220V AC4412 bitRS48593*95*82mm

Terminal wiring diagram

S08XA2-e.jpg

Product AI specification

ItemVoltage InputCurrent Input
Input range-10V ~
+10V
0V ~
+10V
0V ~
+5V
1V ~
+5V
0 ~
20mA
4 ~
20mA
Resolution5mV2.5mV1.25mV1.25mV5μA5μA
Input impedance6MΩ250Ω
Max input range±13V±30mA
Input indicationLED light means normal, dark means break OFF
Response time5ms/4 Channel
Digital input range12 bits, Code range: 0~32000(H series module 16 bits A/D convert)
Precision0.2% F.S
Power supplyMPU use internal power supply, Extension module use external 
power supply 24VDC ±10% 5VA
Isolation modeOpto-electric isolation, Non-isolation between Channel ,between analog and digital
 is opto-electric isolation
Power consumption24VDC ±20%,100mA(Max)

Analog input (AI) wiring diagram

Haiwell Industry Automation

Product AO specification

ItemVoltage OutputCurrent Output
Output range-10V ~
+10V
0V ~
+10V
0V ~
+5V
1V ~
+5V
0 ~
20mA
4~20mA
Resolution5mV2.5mV1.25mV1.25mV5μA5μA
 Output load impedance1KΩ@10V≥500Ω@ 5V≤500Ω
Output indicationLED light means normal
Drive capability10mA
Response time3ms
Digital output range12 bits, Code range: 0~32000(H series module 16 bits D/A convert)
Precision0.2% F.S
Power supplyMPU use internal power supply, Extension module use external 
power supply 24VDC ±10% 5VA
Isolation modeOpto-electric isolation, Non-isolation between Channel, between analog
 and digital is opto-electric isolation
Power consumption24VDC ±20%,100mA(Max)

Analog output (AO) wiring diagram

Haiwell Industry Automation


CR NumberFunction Declare
S08XA2
00H (Read only)The low byte is the module code, and the high byte is the module version number.
01HCommunication address
02HCommunication protocol: The low 4-bit of the low bytes:0 - N,8,2 For RTU1 - E,8,1 For RTU
2 - O,8,1 For RTU
3 - N,7,2 For ASCII4 - E,7,1 For ASCII5 - O,7,1 For ASCII6 - N,8, 
1 For RTU       
The high 4-bit of the low bytes: 0 – 24001 – 48002 – 96003 – 192004 – 38400
5 – 57600
6 - 115200
03H~06HExtend module name
07H~08HDefault IP address: 192.168.1.111
09~0AH (Read only)Reserve
0BHHigh byte subnet mask(b3~b0,1 indicates 255,0 indicates 0 , for example, subnet mask 
255.255.255.0, b3~b0=1110), low byte Reserved
0CH~0EH (Read only)Reserve
0FH (Read only)Error code: 0-Normal, 1-Illegally firmware identity, 2-Incomplete firmware, 3-System data access
 exception, 4-No external 24V power supply
10H (Read only)The input value of channel 1
11H (Read only)The input value of channel 2
12H (Read only)The input value of channel 3
13H (Read only)The input value of channel 4
14HThe signal type of intput channel 1, note 2
15HThe signal type of intput channel 2, note 2
16HThe signal type of intput channel 3, note 2
17HThe signal type of intput channel 4, note 2
18HUse the engineering value mark, note 6
19HThe lower limit in engineering value of input channel 1
1AHThe lower limit in engineering value of input channel 2
1BHThe lower limit in engineering value of input channel 3
1CHThe lower limit in engineering value of input channel 4
1DHThe upper limit in engineering value of input channel 1
1EHThe upper limit in engineering value of input channel 2
1FHThe upper limit in engineering value of input channel 3
20HThe upper limit in engineering value of input channel 4
21HThe sampling frequency of input channel 1, note 1
22HThe sampling frequency of input channel 2, note 1
23HThe sampling frequency of input channel 3, note 1
24HThe sampling frequency of input channel 4, note 1
25HThe zero point correction value of input channel 1
26HThe zero point correction value of input channel 2
27HThe zero point correction value of input channel 3
28HThe zero point correction value of input channel 4
29H (Read only)Channel 1~4 input disconnection alarm, note 5
2AHThe output value of output channel 1  
2BHThe output value of output channel 2
2CHThe output value of output channel 3
2DHThe output value of output channel 4
2EHThe signal type of output channel 1, note 2
2FHThe signal type of output channel 2, note 2
30HThe signal type of output channel 3, note 2
31HThe signal type of output channel 4, note 2
32HUse the engineering value mark, note 6
33HThe lower limit in engineering value of output channel 1
34HThe lower limit in engineering value of output channel 2
35HThe lower limit in engineering value of output channel 3
36HThe lower limit in engineering value of output channel 4
37HThe upper limit in engineering value of output  channel 1
38HThe upper limit in engineering value of output  channel 2
39HThe upper limit in engineering value of output  channel 3
3AHThe upper limit in engineering value of output  channel 4
3BHThe power-off output mark, note 8
3CHThe power-off output value of output channel 1
3DHThe power-off output value of output channel 2
3EHThe power-off output value of output channel 3
3FHThe power-off output value of output channel 4
40H (Read only)Output channel indicator, note 7
41H (Read only)Reserve
42H~4FH (Read only)

Note: 

1. Sampling frequency:0 - 2 times、1 - 4 times、2 - 8 times、3 - 16 times、4 - 32 times、5 - 64 times、6 - 128 times、7 - 256 times

2. Signal type:0 - [4,20]mA、1 - [0,20]mA 、2 - [1,5]V、3 - [0,5]V、4 - [0,10]V、5 - [-10,10]V

3. The signal type of thermal resistance:0 - Pt100、1 - Pt1000、2 - Cu50、3 - Cu100

4. The signal type of thermocouple:0 - S、1 - K、2 - T、3 - E、4 - J、5 - B、6 - N、7 - R、8 – Wre3/25、9- Wre5/26、10 - [0,20]mV、11 - [0,50]mV、12 - [0,100]mV

5. Disconnection alarm:Each bit indicates 1 channel, 0-normal, 1-disconnection

6. Use the engineering value mark:Each bit indicates 1 channel, 0-No, 1-Yes

7. Channel indicator status:Each bit indicates 1 channel, 0-off, 1-on

8. Power-off output mark:Each bit indicates 1 channel, 0-No, 1-Yes

9. The output flag while power supply lost: each bits signify 1 Channel ,0-No,1-Yes