Thermal resistance(AI)specification
| Item | Thermal Resistance | |||
| Input range | Pt100 | Pt1000 | Cu100 | Cu50 | 
| Resolution | 0.1℃ | |||
| Input impedance | 6MΩ | |||
| Input indication | LED light means normal, dark means break OFF | |||
| Response time | 560ms/4 Channel, 880ms/8 Channel | |||
| Digital input range | 16 bits, Code range: 0~32000 | |||
| Precision | 0.1% F.S | |||
| Power supply | MPU use internal power supply, Extension module use external  power supply 24VDC ±10% 5VA  | |||
| Isolation mode | Opto-electric isolation, Non-isolation between Channel ,between  analog and digital is opto-electric isolation  | |||
| Power consumption | 24VDC ±20%, 50mA(Max) | |||
Thermocouple(AI)specification
| Item | Thermocuople input | 
| Input range | S,K, T, E, J ,B, N, R, Wre3/25, Wre5/26, [0-20]mV, [0-50]mV, [0-100]mV | 
| Resolution | 0.1℃ | 
| Input impedance | 6MΩ | 
| Max range | ±5V | 
| Input indication | LED light means normal, dark means break OFF | 
| Response time | 560ms/4 Channel, 880ms/8 Channel | 
| Digital input range | 16 bits, Code range: 0~32000 | 
| Precision | 0.1% F.S | 
| Power supply | MPU use internal power supply, Extension module use external  power supply 24VDC ±10% 5VA  | 
| Isolation mode | Opto-electric isolation, Non-isolation between Channel ,between  analog and digital is opto-electric isolation  | 
| Power consumption | 24VDC ±20%, 50mA(Max) | 
Thermocouple and RTD Input wiring diagram