Xiamen Haiwell Technology Co., Ltd.

请上传logo 请上传logo

Haiwell PLC-Analog input and output specifications and wiring

2015-02-12 14:00:05 haiwell

Analog input (AI)specification

ItemVoltage InputCurrent InputRTD InputThermocouple Input
Input range-10V ~
+10V
0V ~
+10V
0V ~
+5V
1V ~
+5V
0 ~
20mA
4 ~
20mA
Pt100
Pt1000
Cu50
Cu100
S, K, T, E, J, B, N, R, 
Wre3/25, Wre5/26, 
[0-20]mV, [0-50]mV,
 [0-100]mV
Resolution5mV2.5mV1.25mV1.25mV5uA5uA0.10.1
Input impedance6MΩ250Ω6MΩ6MΩ
Max input range±13V±30mA
±5V
Input indicationLED light means normal, dark means break OFF
Response time5ms/4 Channel560ms/4 Channel, 880ms/8 Channel
Digital input range12 bits, Code range: 0~32000(H series module 16 bits A/D convert)16 bits, Code range: 0~32000
Precision0.2% F.S0.1% F.S
Power supplyMPU use internal power supply, Extension module use external 
power supply 24VDC ±10% 5VA
Isolation modeOpto-electric isolation, Non-isolation between Channel ,between analog and digital
 is opto-electric isolation
Power consumption24VDC ±20%,100mA(Max)24VDC ±20%, 50mA(Max)


Analog output(AO)specification

ItemVoltage OutputCurrent Output
Output range-10V ~
+10V
0V ~
+10V
0V ~
+5V
1V ~
+5V
0 ~
20mA
4~20mA
Resolution5mV2.5mV1.25mV1.25mV5uA5uA
 Output load impedance1KΩ@10V≥500Ω@ 5V≤500Ω
Output indicationLED light means normal
Drive capability10mA
Response time3ms
Digital output range12 bits, Code range: 0~32000(H series module 16 bits D/A convert)
Precision0.2% F.S
Power supplyMPU use internal power supply, Extension module use external 
power supply 24VDC ±10% 5VA
Isolation modeOpto-electric isolation, Non-isolation between Channel, between analog
 and digital is opto-electric isolation
Power consumption24VDC ±20%,100mA(Max)